JF Smoke Extraction Jet Fans

JF Smoke Extraction Jet Fans

Available in Standard and ATEX Versions

Manufacturing Features:
Axial jet fan with galvanised steel casing.

The connection box is accessible by the side from a removable door.
Silencers are filled with mineral wool with high acoustic absorption properties, preventing most of the fan noise to be propagated.The silencer casing is made of galvanised steel. 
Inner duct made of perforated galvanised steel sheet. 
Standard asynchronous squirrel-cage motor with IP-55 protection and Class H insulation, Certified 400ºc/2h. Standard voltages 400V(Y) 50Hz for 1 speed motors and 400V 50Hz for 2 speed motors.

F400 certified induction fans designed

For Effective Ventilation Inside the Fire Danger Zone

Effective smoke extraction utilises induction fans, also known as jet fans, for installation inside the fire danger area where the span of the building is too great for simple ventilation. JF jet fans are commonly installed in car parks and large spaces where polluted air, or smoke from an accidental fire, needs to be removed effectively. 

Highly Effective Silencers for Low Noise Operation

F400 jet fans feature highly effective silencers which are filled with mineral wool with high acoustic absorption properties, preventing most of the fan noise to be propagated.

Available Fan Types

JF F400: Long Range Jet Fan with 1 x Axial Fan and 2 x Silencers

Suitable Applications

• Large spaces where polluted air, or smoke from an accidental fire, needs to be removed effectively
• car parks
• Maximum working temperature: 60ºC

Available on Request

• ATEX rated versionsATEX rated fans

Unidirectional JF F400 UN is equipped with a protection guard at the inlet side and a deflector at the outlet. The deflector directs the air away from the ceiling and obstacles like beams or ducting, sweeping the whole volume of air to the closest extraction point.


Reversible JF F400 RE is equipped with protection guards on both sides.

Technical Data

JF fans are paired with a standard asynchronous squirrel-cage motor CERTIFIED 400ºc/2h and manufactured with standard voltages: 400V(Y) 50Hz for 1 speed motors 
and 400V 50Hz for 2 speed motors. Motors offer IP-55 protection and Class H insulation.

Fan Type Voltage
(V)
Frequency
(Hz)
Input
Power (kW)
Rated
Current (A)
Speed
(rpm)
Max Temp
(°C)
IP Rating
(IP)
GKHM 355-CIG.102.5HF IE Gen3 (IE5) 3~ 380-480 50 / 60 2.33 3.7 at 400V 3120 40 IP54
GKHM 400-CIG.114.6FF IE Gen3 (IE5) 3~ 380-480 50 / 60 4.48 7 at 400V 3170 40 IP54
GKHM 450-CIG.128.6IF IE Gen3 (IE4) 3~ 380-480 50 / 60 5.9 9.05 at 400V 2950 40 IP54
GKHM 500-CIG.143.6NA IE Gen3+ (IE4) 3~ 380-480 50 / 60 7.48 11.4 at 400V 2625 40 IP54
GKHM 560-CIG.160.6NA IE Gen3+ (IE4) 3~ 380-480 50 / 60 6.85 10.7 at 400V 2125 40 IP54
GKHM 630-CIG.180.6NA IE Gen3+ (IE4) 3~ 380-480 50 / 60 5.1 7.88 at 400V 1580 40 IP54